Easco Boiler Corp. | Field Erected & Packaged Quality Steel Boilers A Division of THE A.L. EASTMOND & Sons Corporation
Scotch Marine Boilers
pdf NY City MEA Numbers (PDF - 132KB)
All Categories > MODEL FPS - FOUR PASS SCOTCH MARINE BOILER > Item # FPS-700  

Item # FPS-700, MODEL FPS - FOUR PASS SCOTCH MARINE BOILER


EASCO Four pass scotch marine design has higher thermal efficiency, up to 3% more efficient than a 3-pass boiler design. EASCO FPS model is wet back fire tube is designed to increase longevity and enhanced durability, has larger steam space and disengaging area. Available in 15psig steam and up to 160psig water design, submersible tank less Domestic Hot water coils are optional.

  • High Efficiency
  • Low Heat Release
  • Low Furnace Pressure
  • 5 Square Feet of Heating Surface per Boiler Horsepower
  • Large Steam Space and Disengaging Area





  • Boiler Rating  · Characteristic Data  · Boiler Dimensions  · Boiler Service Connection Locations  · Boiler Service Connection Sizes

    Boiler Rating

    Horse Power

    700 bhp

    Steam or Hot Water

    23,433 mbh

    Steam, @ 212 F

    24,150 pph

    Natural Gas, @ 1,000 btu/ft3

    28,576 cfh

    Light Oil, @140,000 btu/gal

    201.65 gph

    Heavy Oil, @ 150,000 btu/gal

    190.5 gph


    Characteristic Data

    Heating Surface, Fireside

    3,500 sf

    Furnace Volume

    231.7 cf

    Furnace Heat Release Rate

    123,357 bcfh

    Steam Disengaging Area

    114.6 sf

    Steam Space

    146.8 cf

    Water Content, Steam Application

    3,444 gal

    Water Content, Water Application

    4,542 gal

    Shipping/Dry Weight, Approx.

    48,100 lb

    Operating/Wet Weight, Approx.

    85,900 lb


    Boiler Dimensions

    A - Overall Length

    View
    277 9/16 in

    A' - Overall Length w/o Burner

    View
    237-7/8 in

    B - Shell Length

    View
    191 in

    C - Tube Removal Clearance

    View
    197 in

    D - Rear Door Swing Clearance

    View
    72-3/4 in

    E - Platform Length

    View
    68-3/4 in

    F - Skid Length

    View
    243-1/2 in

    G - Fr. Saddle Location

    View
    16 in

    H - Distance Between Saddles

    View
    146-3/4 in

    I - Saddle Side Width

    View
    12 in

    J - Overall Width

    View
    133-1/2 in

    J' - Overall Width, w/o Trims

    View
    115-1/8 in

    K-Saddle Front Width

    View
    78 in

    L - Overall Height

    View
    146-5/8 in

    M - Normal Water Line

    View
    100-7/16 in

    N - Boiler Center Height

    View
    67-7/16 in

    0 - Furnace Center Height

    View
    41-7/16 in

    P - Shell Bottom Clearance

    View
    12 in

    Q - Skid Height

    View
    6 in


    Boiler Service Connection Locations

    R - Supply C.L. to Shell Front End

    View
    54 in

    S-Supply Height

    View
    128-7/8 in

    T - Return C.L. to Shell Front End

    View
    136 in

    U - Return Height

    View
    24 in

    V - Flue Outlet C.L. to Shell Front End

    View
    15 in

    W - Flue Outlet Height

    View
    126.5625 in


    Boiler Service Connection Sizes

    a - Supply, Steam/Hot Water

    View
    12/10 NPS

    b - Flue Outlet

    View
    28 in

    c - Safety Valves

    View
    3 NPT

    d - Control Header

    View
    1 NPT

    e - Surface Blowdown

    View
    2-1/2 NPT

    f - Washout

    View
    2-1/2 NPT

    g - Return & FW, Steam/Hot Water

    View
    6/10 NPS

    h - Bottom Blowdown

    View
    2-1/2 NPT

    i - Aquastat

    View
    3/4 NPT

    j - Oil Preheater, Optional

    View
    2-1/2 NPT

    k - Top inspection/Manhole Access

    View
    12x16 NPT


        Download PDF Download PDF   
        border="0" Printable Page  
        Email Email This Page  
        Save To Favorites Save To Favorites
      

     MORE IMAGES 

    ·  Model FPS Drawing 1

    ·  Model FPS Drawing 2


    Site created by ThomasNet Web Solutions and powered by Navigator Platform