Easco Boiler Corp. | Field Erected & Packaged Quality Steel Boilers A Division of THE A.L. EASTMOND & Sons Corporation
Scotch Marine Boilers
pdf NY City MEA Numbers (PDF - 132KB)
All Categories > SERIES ESP - LOW PRESSURE STEAM AND HOT WATER SCOTCH MARINE BOILER > Item # ESP-175  

Item # ESP-175, SERIES ESP - LOW PRESSURE STEAM AND HOT WATER SCOTCH MARINE BOILER


EASCO Series ESP, Steel Scotch Marine, Horizontal Firetube 3-Pass Waterbacked Combustion Systems are manufactured for use in low-pressure steam (15 PSIG) or hot-water (30 to 160 PSIG, maximum 250 degrees F) applications, providing for efficient operation and low cost maintenance.




Lengths  · Widths  · Heights  · Boiler Service Connection Locations  · Boiler Service Connection Sizes  · Specifications  · Ratings & Capacity Data

Lengths

A-Overall

272 in

B-Shell

201-1/2 in

C-Base Frame

226 in

D-Service Platform

35 in

E-Minimum Tube Pull Clearance

207-1/2 in

F-Minimum Rear Smoke Box Door Clearance

28 in


Widths

G-Overall

76 in

H-Diameter OD with 2" Insulation

64-5/8 in

l-Base Frame (Package)

44 13/16 in

J-Base Saddle (Field Erect)

48 in

K-Distance to C.L. Front Saddle (Field Erect)

9 in

L-Distance Between Saddles (Field Erect)

173-1/2 in

M-Saddle

8 in

N-Front Smoke Box

8 in


Heights

O-Overall

93 in

P-Base to Furnace C.L.

30-11/16 in

Q-Base Frame

6 in

R-Base to Boiler C.L.

42-5/16 in

S-Bottom of Base Frame to Shell (Package)

12 in

T-Bottom of Saddle to Shell (Field Erect)

12 in


Boiler Service Connection Locations

U-Base to Flue Gas Outlet

77 9/16 in

V-Base to Supply Outlet

80 1/2 in

W-Length from Front Tubesheet to Center of Supply Conn.

36 in

X-Rear Smoke Box Outlet Center Line

13 in

Y-Length from Front Tubesheet to Center of Return Conn.

146 in

Z-Height from Base to Return Connection

18 in


Boiler Service Connection Sizes

a-Supply, Steam/Hot Water

6 in
8
in

b-Flue Gas Vent

20 in

c-Safety Relief Valve(s)

2 in

d-Control Header

1-1/4 in

e-Surface Blowdown

2 -1/2 in

f-Washout

2 -1/2 in

g-Feedwater/Return, Steam/Hot Water

4 in

h-Bottom Blowdown

2 in

i-Aquastat

3/4 in

j-Preheater/Blend Pump

2 -1/2 in


Specifications

Shipping Weight Dry Packaged (Approx.)

21000 lb

Water Content Steam Boiler

1057

Water Content Hot Water Boiler

1308

General Service Access & Fireside Sampling

Manhole
Handhole

Furnace Access Door

Furnace Draft Sample

Flue Gas Outlet Cleanout Access

Furnace Observation Port

Sequence Draft Sample

Combustion Relief Mechanism

Rear Smoke Box Access

Front Smoke Box Access


Ratings & Capacity Data

Gross Output Boiler Horsepower

175 hp

Gross Output Steam/Hot Water

5858 mbh

Gross Output Steam, from and at 212 degrees F

6040 lb/hr

Maximum Firing Rate Light Oil, 140 MBH/Gal

50.40 gph

Maximum Firing Rate Heavy Oil, 150 MBH/Gal

49 gph

Maximum Firing Rate Natural Gas

7323 mbh

Heating Surface Fireside

875 ft²


    Download PDF Download PDF   
    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

 MORE IMAGES 

·  Packaged Boiler Assembly - Right Elevation Drawing

·  Packaged Boiler Assembly - Front View Drawing

·  Packaged Boiler Assembly - Rear View Drawing

·  Field Erect Saddle - Right Elevation Drawing

·  Field Erect Saddle - Front View

·  Series ESP - Low Pressure Steam and Hot Water Scotch Marine Boiler Nomenclature Drawing


Site created by ThomasNet Web Solutions and powered by Navigator Platform