EASCO Series FST, Steel Scotch Marine, Horizontal Firetube 3-Pass Waterbacked Combustion Systems are manufactured for use in low-pressure steam (15 PSIG) or hot-water (30 to 160 PSIG, maximum 250 degrees F) applications, providing for efficient operation and low cost maintenance.




Lengths  · Widths  · Heights  · Boiler Service Connection Locations  · Boiler Service Connection Sizes  · Specifications  · Ratings & Capacity Data

Lengths

A-Overall

246 in

B-Shell

162 3/8 in

C-Base Frame

215 in

D-Service Platform

55 in

E-Minimum Tube Pull Clearance

168 3/8 in

F-Minimum Rear Smoke Box Door Clearance

28 in


Widths

G-Overall

120 in

H-Diameter OD with 2" Insulation

100-7/8 in

l-Base Frame (Package)

71 5/8 in

J-Base Saddle (Field Erect)

76 in

K-Distance to C.L. Front Saddle (Field Erect)

18 in

L-Distance Between Saddles (Field Erect)

115 1/8 in

M-Saddle

10 in

N-Front Smoke Box

12 1/2 in


Heights

O-Overall

130 in

P-Base to Furnace C.L.

42 5/16 in

Q-Base Frame

6 in

R-Base to Boiler C.L.

60-7/16 in

S-Bottom of Base Frame to Shell (Package)

12 in

T-Bottom of Saddle to Shell (Field Erect)

12 in


Boiler Service Connection Locations

U-Base to Flue Gas Outlet

115 in

V-Base to Supply Outlet

116 3/4 in

W-Length from Front Tubesheet to Center of Supply Conn.

36 in

X-Rear Smoke Box Outlet Center Line

17-1/4 in

Y-Length from Front Tubesheet to Center of Return Conn.

99 7/8 in

Z-Height from Base to Return Connection

22 1/4 in


Boiler Service Connection Sizes

a-Supply, Steam/Hot Water

12/6 in

b-Flue Gas Vent

30 in

c-Safety Relief Valve(s)

2-1/2 in

d-Control Header

1-1/4 in

e-Surface Blowdown

2 -1/2 in

f-Washout

2 -1/2 in

g-Feedwater/Return, Steam/Hot Water

6/6 in

h-Bottom Blowdown

2 1/2 in

i-Aquastat

3/4 in

j-Preheater/Blend Pump

2 -1/2 in


Specifications

Shipping Weight Dry Packaged (Approx.)

33000 lb

Water Content Steam Boiler

2060

Water Content Hot Water Boiler

2450

General Service Access & Fireside Sampling

Manhole
Handhole

Furnace Access Door

Furnace Draft Sample

Flue Gas Outlet Cleanout Access

Furnace Observation Port

Sequence Draft Sample

Combustion Relief Mechanism

Rear Smoke Box Access

Front Smoke Box Access


Ratings & Capacity Data

Gross Output Boiler Horsepower

400 hp

Gross Output Steam/Hot Water

13390 mbh

Gross Output Steam, from and at 212 degrees F

13800 lb/hr

Maximum Firing Rate Light Oil, 140 MBH/Gal

115.20 gph

Maximum Firing Rate Heavy Oil, 150 MBH/Gal

112 gph

Maximum Firing Rate Natural Gas

16738 mbh

Heating Surface Fireside

2000 ft²


    Download PDF Download PDF   
    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

 MORE IMAGES 

·  Packaged-Boiler-assembly-Right-elevation

·  Field-Erect-Saddle---Front-View

·  Field-Erect-Saddle---Right-Elevation

·  Series FST - Low Pressure Steam and Hot Water Scotch Marine Boiler Order Nomenclature Drawing


Site created by ThomasNet Web Solutions and powered by Navigator Platform